Coordination between relay protection functions and excitation system with generator capability curve
Vučićević Darko, Buha Danilo, Marinković Savo and 2 more
Zbornik Radova: Elektrotehnički Institut "Nikola Tesla" · 2021
doi:10.5937/zeint31-35025 (opens in a new tab)
We email you when a new notice or a question about this paper appears.
Abstract
It is common practice for relay protection and excitation systems to be adjusted independently. That practice leads to the uncoordinated operation of some protective functions. This article presents the tuning of some important protection functions. The first step is loss of excitation protection adjusting and its coordination with the minimum excitation limiting function. Analyzing the coordination settings of this protection with the minimum excitation limiter in practice, it is often noticed that these functions are inadequately adjusted, so the capacitive part of the generator capability curve is not optimally used. That is in contradiction with the high need for capacitive reactive power in the transmission system. The second step refers to the coordination of the maximum stator current limiter in the excitation system with stator overload protection, overcurrent protection, and permitted generator stator overload. It is noted here that this coordination is often not adequately adjusted, leading to the following irregularities: -malfunction of the automatic voltage regulator in certain operating situations, which can lead to voltage collapse in the transmission system; -in some operating situations, there is no forcing of excitation current when it is most needed to preserve system stability.
Abstract licence: CC BY
Reads
Read by people on this page
None yet.
Checked or read by AI through naulon
None yet.
A person counts once a day per paper. We keep no cookie and no address: a reader is a hash that changes every day. Any month under five reads shows no number.
Are you an author?
Is this your paper?
Claim it to add your note and be paid when agents cite it. Free.