Research on Harmonic Current Amplification Effect of Parallel APF Compensating Voltage Source Nonlinear Load
Xueliang Wei, Cunzhong Li, Mingxuan Qi and 3 more
Energies · 2019
doi:10.3390/en12163070 (opens in a new tab)
We email you when a new notice or a question about this paper appears.
Abstract
A parallel active power filter (APF) is generally used to suppress dynamic harmonic current and compensate reactive power in the grid. However, parallel APF may have a negative effect on the load current when compensating the nonlinear load of a voltage source type, which may lead to the amplification effect of the load harmonic current. In this paper, the fundamental causes of harmonic current amplification were analyzed by studying the harmonic current amplification effect when a parallel APF compensates a nonlinear load. According to the results of the theoretical derivation, a feasible method to limit this current amplification effect by changing the system structure and the APF’s own control was proposed, and the corresponding design scheme is given. Finally, the correctness of the theoretical derivation of the harmonic current amplification effect and the feasibility of the proposed solution were proven through simulation and experiment.
Abstract licence: CC BY
Reads
Read by people on this page
None yet.
Checked or read by AI through naulon
None yet.
A person counts once a day per paper. We keep no cookie and no address: a reader is a hash that changes every day. Any month under five reads shows no number.
Are you an author?
Is this your paper?
Claim it to add your note and be paid when agents cite it. Free.