Equipment for Quantitative Assessment of Control System Performance Using Pseudo-Random Binary Signals

M. S. Beck MSc, CEng, MIEE, F. M. Dadachanji MSc.

Measurement + Control · 1968

doi:10.1177/002029406800100704 (opens in a new tab)

We email you when a new notice or a question about this paper appears.

Abstract

The reasons for requiring an accurate prediction of control system performance under actual operating conditions are discussed. It is shown that a measure of the integral square error in response to a stationary time series disturbance meets most requirements. The analytical approach to calculating integral square error is described and a specific example is given. Apparatus for generating the disturbance signal and measuring the integral square error is described. It is suitable for use with systems having a dominant time constant between one second and several hours. Experimental results for a pressure control system are compared with the theoretically predicted results. The disturbance generator can also be used for generating pseudo-random binary sequences.