Experimental Studies of the Developed Method for Determining the Insulation Parameters in an Asymmetric Network by a Voltage up to 1000 V at Mining Enterprises

Utegulov A. B., Koshkin I. V., Koshkina A. I.

E3S Web of Conferences · 2020

doi:10.1051/e3sconf/202022001032 (opens in a new tab)

We email you when a new notice or a question about this paper appears.

Abstract

In the work experimental studies of the developed method for determining the insulation parameters in an asymmetric electrical network by a voltage up to 1000 V at mining enterprises were carried out. It is based on measuring the module values of line voltage, angle of phase shift between vectors of damaged phase voltage relative to the ground and line voltage at two other phases, as well on measuring the module value of damaged phase voltage relative to the ground before and after connecting additional capacitive conductivity between the network’s phases and the ground. The results of experiment showed that the developed method for determining the insulation parameters has satisfactory accuracy and safety when operating three-phase electrical networks by voltage up to 1000 V at mining enterprises.