Skip to content
naulon
Not checkedNot checked for notices yet.

General earth fault protection for MV networks using wavelet decomposition and Bayesian criterion

Marciniak Lubomir

E3S Web of Conferences · 2019

doi:10.1051/e3sconf/20198402007 (opens in a new tab)

We email you when a new notice or a question about this paper appears.

Abstract

For selective detection of earth faults in medium voltage networks, the general protection can be used, which unlike individual protections controls earth currents in all lines supplied from the substation. To detect high-resistance and arc faults, it is possible to use in such protections the details from wavelet decomposition of earth currents and the Bayesian conditional probability criterion. The paper presents a protection model using details of earth currents and the Bayesian criterion. Significant parameters of the model were determined: sampling frequency, wavelet types and decomposition levels, parameters of the probability density function and decision conditions. The effectiveness of the protection in the case of non-stationary high-resistance short-circuits in the network with natural asymmetry and harmonic distortion was also assessed.

Abstract licence: CC BY

Reads

Read by people on this page

None yet.

Checked or read by AI through naulon

None yet.

A person counts once a day per paper. We keep no cookie and no address: a reader is a hash that changes every day. Any month under five reads shows no number.

Are you an author?

Is this your paper?

Claim it to add your note and be paid when agents cite it. Free.