Numerical Analysis for Smoke Spread in an Aircraft Hangar
Khalil Essam E., Haridy Hatem Kayed, Ahmed Eslam Said Abdelghany and 1 more
E3S Web of Conferences · 2019
doi:10.1051/e3sconf/201911101090 (opens in a new tab)
We email you when a new notice or a question about this paper appears.
Abstract
Smoke is one of the most dangerous factors in aircraft hangar in case of fire. As it causes reduce in visibility and deaths due to high temperature or toxicity also prevents applying evacuation plan for workers. This study present numerical analysis for improving traditional system of ventilation system to manage smoke produced due to push-back vehicle on fire at hangar. By studying effect of changing extraction and supply rates, the number of extraction and supply fans, and the arrangement of extraction and supply fans on the visibility, temperature and air velocity at human level to insure not to exceed limits stated by NFPA 130[1] to apply evacuation plan for workers. The study is performed using Fire dynamic simulator to simulate 16 case studies in the hangar of airports in Brandenburg. The hangar has the outer dimensions of 83.40 m width and 77.60 m depth and thus an inner area of approx. 6,472 m2. The hangar has a medium interior height of approximately 18.20 m. The results show that using extraction fans with rate (ACH) double the supply rate for the traditional ventilation system gives very good results in controlling the smoke. As well as, decreasing the number of supply fans will make the smoke spread rate inside the hangar lower, which helps to control the smoke spread of fire in less time.
Abstract licence: CC BY
Reads
Read by people on this page
None yet.
Checked or read by AI through naulon
None yet.
A person counts once a day per paper. We keep no cookie and no address: a reader is a hash that changes every day. Any month under five reads shows no number.
Are you an author?
Is this your paper?
Claim it to add your note and be paid when agents cite it. Free.