DC protection for a multi-terminal HVDC network including offshore wind power, featuring a reduced DC circuit breaker count

Max A. Parker, Derrick Holliday, Derrick Holliday and 1 more

The Journal of Engineering · 2019

doi:10.1049/joe.2018.8149 (opens in a new tab)

We email you when a new notice or a question about this paper appears.

Abstract

Large offshore wind farms located far from shore, as are being planned or built in the North Sea, will require high-voltage DC (HVDC) transmission to shore, and multi-terminal HVDC could offer further benefits. Currently proposed methods to protect against faults in the DC network are based on extremely fast-acting DC circuit breakers located on all cable ends, leading to high cost. A method is proposed based around discharging the DC network to isolate the fault, which drastically reduces the circuit breaker requirement, while making use of the inherent current-limiting behaviour of the wind turbines. The validity of this approach is demonstrated in simulation.