Determination algorithms of smoke interface height in channel fire simulation: Data comparative analysis and experimental verification
Xi Zhang, Xiaoyuan Dang, Jie Li and 3 more
Case Studies in Thermal Engineering · 2022
doi:10.1016/j.csite.2022.102450 (opens in a new tab)
We email you when a new notice or a question about this paper appears.
Abstract
Smoke layer interface height is an important safety parameter in channel fire accidents. This paper proposed and compared three determination algorithms to estimated smoke layer interface height in channel fire simulation based on the characteristics of smoke layer interface during one-dimensional propagation stage. Reduced-scale experiments were also conducted to verify the predicted results. Results show that the dis-alignment of pressure gradient and density gradient, as well as velocity shear could generate vorticity. And vorticity motivates air entrainment of hot smoke. The vorticity at smoke layer interface is the largest in vertical direction. The smoke layer interface could be characterized by vertical component of temperature gradient, the vorticity perpendicular to longitudinal slice and horizontal component of velocity, among which the temperature gradient method was found to be suitable for determining the smoke layer interface height. And the prediction results by temperature gradient method agree with experimental data and empirical results well.
Abstract licence: CC BY-NC
Reads
Read by people on this page
None yet.
Checked or read by AI through naulon
None yet.
A person counts once a day per paper. We keep no cookie and no address: a reader is a hash that changes every day. Any month under five reads shows no number.
Are you an author?
Is this your paper?
Claim it to add your note and be paid when agents cite it. Free.